			      Special Features
						
						
						
							
                                | Q-1 Indoor Environment | 
                                Sound environment                                    	
                                        Sound insulation using soundproof sashes (T-2) Use of rock wool acoustic board (for ceilings) and tile carpet (for floors) as sound absorbing materials  Indoor thermal environment                                    	
                                        Adoption of Low-E glass The coefficient of overall heat transmission, U, of exterior walls and windows of 0.88 W/m2-K and 5.17 W/m2-K, respectively, and the shading coefficient, SC, of windows of 0.38 are ensured by the thermal insulation of exterior walls. Air handling units (AHUs) are laid out separately and decentrally (8 sets per standard floor) with respect to each orientation and minimum compartment. Cooling/heating operation is selectable and controllable with respect to each minimum compartment. The use of the atrium in the common area of the office for the pathway of exhaust air to reduce heat load in the corridors, shorten the length of the pathway, and reduce the power required to discharge the exhaust air.  Light and visual environments                                    	
                                        Incorporation of a daylighting system (T-Soleil) that moves in response to the outside environment to let natural light in corridors Daylight control using vertical louvers and horizontal blinds Average illuminance of 750 lux or more (779 lux) in the office  Indoor air quality                                    	
                                        Use of finishing materials rated as F☆☆☆☆ and free of volatile organic compounds (VOCs), such as xylene and toluene Outside air taken into the building from top of the building through an equipment void. A clearance of 6 m or more ensured between the exhaust opening and fresh air inlet  | 
							
                                | Q-2 Quality of Service | 
                                Functionality
                                    	A floor area of not less than 9 m2/occupant ensured in the officeAdoption of free access floor in the office to easily replace wiringCeiling heights of 2.95 m and 3.8 m ensured in the office on the standard floors and in the retail premises on the 1st to 3rd floors, respectivelyLayout of smoking room and refreshment space (no smoking) on the standard floorsPreparation of interior perspectives and mockups for the study of interior and color plans Durability and reliability
                                    	High safety with our own structural system that combines seismic isolation and seismic response control systemsAdoption of damage control design and seismic isolation structureAdoption of a reliable three-line spot network power reception system for the substation. Installation of emergency power generatorAdoption of water-saving toilet bowl and urinal (automatic flushing with motion sensor), automatic water faucet and a function to produce a flushing sound Adaptability and maintainability
                                    	Story height of 4,150 mm on the standard floors, 6,500 mm on the 1st and 2nd floors and 6,000 mm on the 3rd floor in the low-rise sectionFloor load of 4,900 N/m2 on the safe side on the standard floorsAir-conditioning and water supply pipes that can be easily replaced by using the equipment void and air-conditioning machine room on each floor (at 8 locations)Layout of electric pipe shaft (EPS) in consideration of maintainability. Adoption of integrated ceiling and free access floor in corridors and office for easy replacement of cables | 
							
                                | Q-3 Outdoor Environment on Site | 
                                Conservation and creation of biological environment
                                    	Creation of rich spaces for creatures to live using large open spacesFormation of networks of greenery connecting to surrounding green zones by introducing endemic species that are seen in potential natural vegetationLayout of trees and consideration of tree types suitable for environmental conditions (including salt tolerance)Setting of indicator species attracting organisms based on the results of bio-assessment around the project site. Provision of spaces to attract birds and butterflies and planting of trees that provide food and ground covers Consideration of townscape and environment
                                    	Layout plan that considers the buildings constructed before this building in the same block, the landscape having a harmonic unity, and the formation of a skyline that goes up gently at the top of buildingsBlue and white exterior appearance forms an impression of Minato Mirai District in YokohamaExterior design based on vertical lines having a sense of future-oriented rise and a sense of unity with the buildings constructed ahead of this building in the same blockLarge open space such as a courtyard at the center of the block in coordination with adjacent buildingsIncrease in the ratio of green coverage with plants of different heights, such as tall trees, bushes, and ground covers, and the create a comfortable landscape with four seasons Consideration of regional characteristics and amenity
                                    	Pilotis laid out on the periphery of the building at the Keyaki-dori Ave. side to provide urban spaces to take shelter from rain and meet someone, contributing to improving amenityLayout of a variety of open spaces, including recreation spaces such as flower garden, open lawn space, and bustling open spaces such as pergolaConstruction of access path to Minato Mirai Station that is available even when the building is closed to improve convenience and strengthen the networks of bustleConstruction of an inner mall in the building to form an intermediate area between Keyaki Street and courtyard (garden) | 
							
                                | LR-1 Energy | 
                                Protection of water resources
                                    	Use of water-saving plumbing fixturesUse of rainwater for watering plants on the roof Use of natural energy
                                    	Installation of a daylighting system (T-Soleil) Highly efficient equipment and systems
                                    	Reduction of ERR by 29.8% and CO2 emissions by 32% (calculated from the CASBEE 2008 Edition)Air-conditioning: Adoption of a district heating and cooling system, variable air volume (VAV) and variable water volume (VWV) systems, and total heat exchangerVentilation: Start/stop control ventilation fan using thermostat and inverter control of ventilation fan in the machine roomLighting: Adoption of highly efficient high-frequency (HF) fluorescent light, and motion sensor controlHot water supply: Individual hot water supply systemElevator: Adoption of a variable voltage variable frequency (VVVF) control systemInstallation of a daylighting system (T-Soleil) Efficient operation
                                    	Evaluation of system efficiency using the energy management function of a building energy management system (BEMS)Plan for basic operation and maintenance policies. Promotion of measures to reduce energy consumption based on the plan-do-check-action (PDCA) cycle | 
							
                                | LR-2 Resources and Materials | 
                                Protection of water resources
                                    	Use of water-saving plumbing fixturesUse of rainwater for watering plants on the roof Materials that lessen impact on the environment
                                    	Use of electric furnace steel for beams, and blast furnace concrete for building foundationsUse of recycled materials for free access floor and interlocking concrete block pavement for exteriorsBuilding structural frames are prestressed concrete (PC) with paint finish, and windows are unit curtain walls (CWs). They can be taken apart.Recyclable unit members (free access floor and integrated ceiling)Use of thermal insulation materials having zero ozone depletion potential (ODP) and global warming potential (GWP) of less than 50Use of R410 and R404A having zero ODP for the refrigerant of air-cooled air conditioner and refrigerant | 
							
                                | LR-3 Off-site Environment | 
                                Air pollution control
                                    	Introduction of a district heating and cooling system Prevention of noises, vibrations and malodors
                                    	Outdoor installation of all fans except one exhaust fan. Noise levels below the current standards of the Noise Regulation Act Control of wind damage and sunlight obstruction
                                    	The ranking of the building by the wind environment assessment is partly higher than the ranking of the site location. Light pollution control
                                    	Outdoor lighting plan in compliance with the Guidelines for Countermeasures against Light PollutionAdoption of Low-E glass with an opening ratio of less than 50% and low reflectivity Indoor thermal environment
                                    	Layout of building and planning for open spaces in consideration of the prevailing wind direction in summer. Reduction in artificial exhaust heat by the use of a district heating and cooling systemShaded area accounting for 21.26% of the lot area, a ratio of green coverage of 13.47%, and a ratio of green coverage on the roof of 21.47%Confirmation of the effects of the wind on the building through computer simulation of the wind environment Control of the effects of impact on district infrastructures
                                    	Planning for the location of an entrance to and exit from the car park and the location of the bicycle park with consideration given to the surroundingsActive reduction and recycling of waste | 
						
						
						Other Features
						
					 
			   
			 
			
			
			
			These cases are described based on assessment results obtained using 
CASBEE.
			CASBEE is a method for rating the environmental performance of buildings using 
			Building Environmental Efficiency (BEE) as an indicator, which is based on the results of 
			separate scores obtained for Q-1~Q-3 (Quality) and LR-1~LR-3 (Load Reduction).